l12 ocean reef.

which glass is worth paying for? we simulated this house in panamá with the three glass options the supplier offered. double glass lets in half the heat and cuts the a/c electricity by 10%.

// 16∶9 hero · ocean reef, panamá
location
ocean reef, panamá
year
2023
typology
residential
status
unbuilt
role
glass study + building performance simulation
architecture: forza creativa
−46%
// the result

heat through the glass in a year, single glass to the optimized mix.

simulated with the tocumen climate, rerun in 2026. architecture by forza creativa, study by entrópica.

// the project

what was asked, and how it was solved.

// brief

l12 ocean reef is a three-level house in panamá with 173 m² of glass. the supplier, profil 2000 / metra, offered three options: single glass, double selective glass, and the same double glass with an acoustic layer.

// the answer

the answer was a mix: acoustic glass in the living areas and the master suite, double glass in the bedrooms, and single glass in the kitchen and service rooms. the mix gets 91% of the saving of double glass everywhere.

the acoustic glass keeps out the heat just like the double glass. what you pay extra for is quiet.

// key numbers

the study in six numbers.

valuewhat it means
−46%heat through the glass in a year, single glass to the optimized mix
−10%a/c electricity, family of two (19,849 to 17,870 kWh a year)
1,979 kWhless a/c electricity a year, family of two
+6.2 ptscomfortable hours without a/c, whole house
91%of the saving of double glass everywhere, with single glass only in the service rooms
6 dBmore sound reduction from the acoustic glass, at the same heat result
// the study
01

half the heat through the glass

the heat that comes in through the glass in a year, by facade. with the mix it drops from 73.1 to 39.8 MWh. the east facade gains the most.

single glass everywhereoptimized mix
heat gain through the glass (MWh a year)
single glass everywhereoptimized mix
north25 m² 7.1 MWh3.5 MWh
east50 m² 35.8 MWh18.3 MWh
50 m² of glass. the mix keeps single glass in a few service rooms here: 18.3 MWh, against 16.8 with double glass everywhere
south69 m² 17.6 MWh8.9 MWh
west29 m² 12.6 MWh9.1 MWh
29 m² of glass. the mix keeps single glass in a few service rooms here: 9.1 MWh, against 5.9 with double glass everywhere
02

a tenth less air-conditioning

the a/c electricity month by month, for a family of two. the mix uses less every month: from 19,849 to 17,870 kWh a year. the glass is only one source of heat.

single glass everywhereoptimized mix
a/c electricity, family of twomonth
monthsingle glass everywhereoptimized mix
jan1,590.5 kWh1,400.9 kWh
feb1,536.3 kWh1,338.8 kWh
mar1,783.8 kWh1,552.5 kWh
apr1,966.9 kWh1,748.9 kWh
may1,781.1 kWh1,616.6 kWh
jun1,600.7 kWh1,469.7 kWh
jul1,873.8 kWh1,719.9 kWh
aug1,659.5 kWh1,523.4 kWh
sep1,590.7 kWh1,455.1 kWh
oct1,550.4 kWh1,411.3 kWh
nov1,358.9 kWh1,235.3 kWh
dec1,556.8 kWh1,397.8 kWh
03

room by room

comfortable hours without a/c, room by room. the rooms with the most glass gain the most: the living room, 11.3 points.

single glassoptimized mix
comfortable hours without a/c (% of the year)
single glassoptimized mixchange
atrium / stair83.6%94.7%+11.0
living / dining82.8%94.2%+11.3
kitchen91.7%93.4%+1.6
guest room, ground floor82.3%89.0%+6.7
bedroom 384.3%87.9%+3.6
master bedroom78.8%85.6%+6.8
bedroom 280.3%84.0%+3.7
bedroom 178.5%83.4%+4.8
guest room, top floor69.7%74.6%+4.9
den / office68.7%72.1%+3.4
gym64.9%70.1%+5.2
04

where each glass goes

where each glass goes in the mix. sets 1 and 2 keep out the same heat; set 1 adds 6 dB of quiet.

glass area in the optimized mix (m²)
glass area in the optimized mix (m²)
set 1acoustic double 74.1 m²
ug 1.1 W/m²K · g 0.40 · rw 43 dB. living areas and master suite
set 2double 79.8 m²
ug 1.1 W/m²K · g 0.40 · rw 37 dB. bedrooms, den and gym
set 3single 18.9 m²
ug 5.6 W/m²K · g 0.84 · rw 32 dB. kitchen, laundry and service rooms
// method and data

how we got the numbers.

  • model: the house as designed in 2023: 30 rooms, 173 m² of glass in 29 real windows, the louvers and celosías. energyplus 24.2 through honeybee (2026 rerun).
  • glass: supplier sheet values (profil 2000 / metra) at the center of the glass (sets 1 and 2: ug 1.1 W/m²K, g 0.40; set 3: ug 5.6 W/m²K, g 0.84). frames are not modeled.
  • walls: hollow block with a ventilated facade (ground floor) or eifs (upper floors). roof: concrete slab, no insulation. ground at the weather-file ground temperature.
  • a/c: family of two, a/c at 24 °C only where and when they are. electricity = cooling load / cop 3.2 (assumed, same for all cases). full house (10 people) as a check.
  • comfort: the same house with no a/c and half of each window open when inside > 24 °C and outside < 32 °C. ashrae 55 adaptive, 80% limits (± 3.5 °C), still air.
  • weather: tocumen 787920 typical year.
  • check: in 2026 we reviewed the 2023 study. the 2023 model used library glass, generic windows and the airport wind as indoor air speed, so we rebuilt it.

glass study and graphics: entrópica. architecture: forza creativa. glass: profil 2000 / metra. tools: energyplus, ladybug tools (honeybee), python.